Vertiv Liebert GXT MT+EX 3KVA Online UPS
Specification
| Main Feature | |
| Capacity | 3000VA |
| Display Type | LCD Display |
| Load Capacity | 2700 W |
| Input Voltage | Nominal Voltage: 230 Vac Low Line Transfer (Voltage Range): 180 Vac/160 Vac/140 Vac/120 Vac ± 5% (Ambient Temperature < 35 °C) (Based on load percentage 100% to 80%; 80% to 70%; 70% to 60%; 60% to 0%) Low Line Comeback (Voltage Range): 195 Vac/175 Vac/155 Vac/145 Vac ± 5 % (Ambient Temperature < 35 °C) (Based on load percentage 100% to 80%; 80% to 70%; 70% to 60%; 60% to 0%) High Line Transfer (Voltage Range): 300 Vac ± 5>#br###High Line Comeback (Voltage Range): 290 Vac ± 5>#br###Frequency Range: 40 Hz to 70 Hz Power Factor: ≥ 0.99 @ 100% load |
| Output Voltage | Nominal Voltage" 208* Vac/220 Vac/230 Vac/240 Vac AC Voltage Regulation: ± 1>#br### Frequency Range (Synchronized Range): (47 Hz to 53 Hz) or (57 Hz to 63 Hz) Current Crest Ratio: 3 : 1 (maximum) Harmonic Distortion: ≤ 3 % THD (Linear Load), ≤ 6 % THD (Non-linear Load) Transfer Time: Bypass to Inverter (Line mode): Zero Transfer Time: Inverter to Bypass (Line mode): 4 millisecond (ms) (Typical) Waveform (Battery Mode): Pure Sine wave Efficiency on AC to AC mode @ 100% load: 90>#/td### |
| Frequency (Battery Mode) | (50 Hz ± 0.25 Hz) or (60 Hz ± 0.3 Hz) |
| Noise Level | Less than 50 dBA @ 1 meter (m) |
| Battery | Battery Type (Standard Run Model): 12 V/9 Ah Numbers (Standard Run Model): 6 Typical Recharge Time (Standard Run Model): 4 hours recovery to 90% capacity (Typical) Charging Current (maximum) (Standard Run Model): 1.0 A Charging Voltage (Standard Run Model): 82.1 Vdc ± 1>#br Charging Current (Long Run Model): 1.0 A/2.0 A/4.0 A/6.0 A (6.0 A by default) Float Charging Voltage (Long Run Model): 82.1 Vdc ± 1>#/td> |
| Alarm | Battery Mode: Sounding every 4 seconds Low Battery: Sounding every second Overload: Sounding twice every second Fault: Continuously sounding |
| Indications | LCD: Panel UPS status, load level, battery level, input/output voltage, discharge timer, and fault conditions |
| Others | Environment: Operation Humidity and Temperature: 20% to 90% RH @ 0 °C to 50 °C** (non-condensing) Noise Level: Less than 50 dBA @ 1 meter (m) Management: Smart RS232/USB: Supports Windows 2000/2003/XP/Vista/2008, Windows 7, Linux, Unix, and MAC Optional SNMP: Power management from SNMP manager and web browser |
| Input Features | |
| Frequency | 40 to 70 Hz |
| Power Factor | ≥ 0.99 @ 100% load |
| Voltage Range | Low Line Transfer (Voltage Range): 180 Vac/160 Vac/140 Vac/120 Vac ± 5% (Ambient Temperature < 35 °C) (Based on load percentage 100% to 80%; 80% to 70%; 70% to 60%; 60% to 0%) Low Line Comeback (Voltage Range): 195 Vac/175 Vac/155 Vac/145 Vac ± 5 % (Ambient Temperature < 35 °C) (Based on load percentage 100% to 80%; 80% to 70%; 70% to 60%; 60% to 0%) High Line Transfer (Voltage Range): 300 Vac ± 5>#/td### |
| Output Features | |
| Voltage Range | 208 Vac/220 Vac/230 Vac/240 Vac |
| Type of Wave | Pure Sine wave |
| Transfer Time | Transfer Time: Bypass to Inverter (Line mode): Zero Transfer Time: Inverter to Bypass (Line mode): 4 millisecond (ms) (Typical) |
| Physical Specification | |
| Dimension | (Standard Run Model) Dimension, D x W x H (mm): 421 x 190 x 318 (Long Run Model) Dimension, D x W x H (mm): 397 x 145 x 220 |
| Weight | (Standard Run Model) Net Weight (kg): 27.6 (Long Run Model) Net Weight (kg): 7.4 |
| Manufacture Warranty | |
| Warranty | 1 Year (UPS), 6 Months (Battery) |